Connecting Load Cables - Shindaiwa DGK45F Owner's And Operator's Manual

Diesel engine generator
Table of Contents

Advertisement

 Load Cable Selection Tables
(Ex.) If used voltage is 240 V and voltage drops by 12 V.
Length
100 ft (30 m)
or less
Current
50 A
10
100 A
8
150 A
6
(Ex.) If used voltage is 120 V and voltage drops by 6 V.
Current
10 A
20 A
30 A
50 A
100 A
130 A

7-2. Connecting Load Cables

WARNING : ELECTRIC SHOCK
 Before connecting or disconnecting the load cables to/from the output
terminal, always turn the output circuit breakers to the OFF position, stop the
engine, and remove the starter key.
 Close the output terminal cover before operating.
 Do not insert a pin, needle or other metal object into the receptacle.
 Do not touch the generator if the generator or casing becomes wet during
operation.
CAUTION : FIRE
 Do not connect the generator output to indoor wiring.
< Note >
 When connecting a load, check that the generator output setting, output terminal connection
position, and load power source are all matching.
 If using the N terminal, be careful that the currents of each phase are uniform.
 If using three-phase output simultaneously with a single-phase three-wire type output, use in a
range where the total current does not exceed the rated current.
 If using three-phase output simultaneously with a single-phase three-wire type output, be careful
as it is possible for the outputs to mutually affect each other.
 Use proper tools when connecting a load to sufficiently tighten the connection. Failure to
sufficiently tightened will result in cable burnout.
 Terminal cover must remain closed during operation or breaker will trip.
Three-phase: Cabtyre cables
200 ft
300 ft
(61 m)
(91 m)
8
4
2
Single-phase Cabtyre cables
Length
200 ft (61 m)
or less
10
8
6
4
1
1/0
400 ft
(122 m)
6
4
2
1
1
1/0
300 ft (91 m)
400 ft (122 m)
8
6
4
2
2/0
3/0
20
(Unit: AWG)
500 ft
600 ft
(152 m)
(183 m)
4
2
1
1/0
2/0
3/0
(Unit: AWG)
8
4
2
1/0
3/0
4/0