4.24.4 3-line monitor selection (Pr. 774 to Pr.776)

For the parameter unit (FR-PU07)/operation panel (FR-DU07), the first, second, and third monitors can be
changed. When using FR-PU07-01, the monitored items, which are set by Pr.774 to Pr.776, can be displayed in
the 3-line monitor.
The Pr.52 DU/PU main display data selection setting is invalid when Pr.774 to Pr.776 ≠ 9999. Monitored item names
are displayed during monitoring (Monitor name display in the 3-line monitor is available only for FR-PU07-01).
Parameter
Name
Number
PU/DU monitor
774
selection 1
PU/DU monitor
775
selection 2
PU/DU monitor
776
selection 3
Setting
Monitor item
1
Output frequency
2
Output current
3
Output voltage
5
Frequency setting value
6
Running speed
8
Converter output voltage
9
Regenerative brake duty
Electronic thermal relay
10
function load factor
11
Output current peak value
Converter output voltage peak
12
value
13
Input power
14
Output power
17
Load meter
20
Cumulative energization time
23
Actual operation time
24
Motor load factor
*1
The monitor is displayed as Pr. 774 = "1," Pr. 775 = "2," and Pr. 776 = "3" when a parameter unit other than FR-DU07 is used.
*2
The monitor is displayed as Pr. 774 = "1," Pr. 775 = "2," and Pr. 776 = "3" when the monitor selection is valid.
*3
The setting is available when using PLC function. Refer to the FR-F700 PLC function programming manual for details of the PLC function.
....
Specifications differ according to the date assembled. Refer to page 399 to check the SERIAL number.
♦ Parameters referred to ♦
Pr. 52 DU/PU main display data selection
Pr. 59 Remote function selection
Pr. 73 Analog input selection
Pr. 79 Operation mode selection
Pr. 133 PID action set point
Pr. 160 User group read selection
Pr. 178 to Pr. 189 (input terminal function selection)
Pr. 190 to Pr. 196 (output terminal function selection)
C2 (Pr. 902) to C7 (Pr. 905) Frequency setting voltage (current) bias/gain
C42 (Pr. 934) to C45 (Pr. 935) (PID control)
Initial
Setting
Value
Range
1 to 3, 5, 6, 8 to
14, 17, 20,
23 to 25, 40 to
9999
42, 50 to 57,
64, 67, 81 to
86, 100, 9999
Setting
25
Cumulative power
40
PLC function user monitor 1
41
PLC function user monitor 2
42
PLC function user monitor 3
50
Power saving effect
51
Cumulative saving power
52
PID set point
53
PID measured value
54
PID deviation
*1
I/O terminal status
55
*1
Option input terminal status
56
*1
Option output terminal status
57
PTC thermistor resistance
64
67
PID measured value 2
81
BACnet reception status
82
BACnet token pass counter
Refer to page 143
Refer to page 98
Refer to page 173
Refer to page 197
Refer to page 263
Refer to page 192
Refer to page 124
Refer to page 130
Refer to page 263
Select the monitored item to be displayed on the first monitor
(first row in the 3-line monitor).
Select the monitored item to be displayed on the second
monitor (second row in the 3-line monitor).
Select the monitored item to be displayed on the third monitor
(third row in the 3-line monitor).
Monitor item
Setting
83
*3
84
*3
85
*3
86
100
9999
How the monitor is displayed when
Pr. 759 = "4," Pr. 774 = "52," Pr. 775 = "53,"
Refer to page 179
Setting of FR-PU07-01
Description
Monitor item
BACnet valid APDU counter
BACnet communication error
counter
Terminal CA output level
Terminal AM output level
Set frequency before
operation
*2
No selection
and Pr. 776 = "54"
4
323