Mitsubishi FR-F720-00046-NA Instruction Manual page 266

Table of Contents

Advertisement

Communication operation and setting
BINARY VALUE
Object
Object Name
Identifier
0
Inverter running
Inverter operation
11
ready
98
Alarm output
99
Fault output
Inverter running
200
reverse
Control input instruction
300
AU
Control input instruction
301
RT
Control input instruction
302
RL
Control input instruction
303
RM
Control input instruction
304
RH
Control input instruction
305
*2
JOG
Control input instruction
306
MRS
Control input instruction
307
*2
STOP
Control input instruction
308
*2
RES
Control input instruction
309
CS
*2
400
Run/Stop
401
Forward/Reverse
402
Fault reset
*1
R: Read only
W: Read/Write (Commandable values not supported)
*2
The following signals cannot be controlled by the network: Jog operation, automatic restart after instantaneous power failure, start self-holding
and reset. Therefore control input instruction JOG, STOP, RES, and CS are invalid in the initial status. When using Control input instruction JOG,
STOP, RES, and CS, change the signals with
available with ReinitializeDevice. )
*3
If communication speed command source is except for NET, the setting value can be written, but not to be applied.
256
Present Value
Access Type
*1
R
Represents inverter running (RUN signal) status.
R
Represents inverter operation ready (RY signal) status.
R
Represents alarm output (LF signal) status.
R
Represents fault output (ALM signal) status.
R
Represents inverter reverse running status.
Controls the function assigned to terminal AU.
C
Setting 1 of this object turns ON the signal assigned to Pr. 184 AU terminal
function selection.
Controls the function assigned to terminal RT.
C
Setting 1 of this object turns ON the signal assigned to Pr. 183 RT terminal
function selection.
Controls the function assigned to terminal RL.
C
Setting 1 of this object turns ON the signal assigned to Pr. 180 RL terminal
function selection.
Controls the function assigned to terminal RM.
C
Setting 1 of this object turns ON the signal assigned to Pr. 181 RM terminal
function selection.
Controls the function assigned to terminal RH.
C
Setting 1 of this object turns ON the signal assigned to Pr. 182 RH terminal
function selection.
Controls the function assigned to terminal JOG.
C
Setting 1 of this object turns ON the signal assigned to Pr. 185 JOG
terminal function selection.
Controls the function assigned to terminal MRS.
C
Setting 1 of this object turns ON the signal assigned to Pr. 187 MRS
terminal function selection.
Controls the function assigned to terminal STOP.
C
Setting 1 of this object turns ON the signal assigned to Pr. 188 STOP
terminal function selection.
Controls the function assigned to terminal RES.
C
Setting 1 of this object turns ON the signal assigned to Pr. 189 RES terminal
function selection.
Controls the function assigned to terminal CS.
C
Setting 1 of this object turns ON the signal assigned to Pr. 186 CS terminal
function selection.
Controls start/stop command. Start command is written after Speed scale
is applied.
C
1: Run
0: Stop
Controls forward/reverse rotation.
C
1: Reverse rotation
0: Forward rotation
Clears fault output status.
C
(Release of an inverter fault without inverter reset is available.)
Pr. 185, Pr. 186, Pr. 188, Pr. 189 (input terminal function selection).
Description
*3
*3
C: Read/Write (Commandable values supported)
(Refer to page 124) (Reset is