Wiring Configuration; Powering Ann-Bus Devices From Auxiliary Power Supply - Honeywell Notifier RP-2001 Instruction Manual

Pre-action/deluge control panel
Table of Contents

Advertisement

Installation

Wiring Configuration

Figure 2.16 illustrates the wiring between the FACP and ANN-BUS devices.

Powering ANN-BUS Devices from Auxiliary Power Supply

Figure 2.17 illustrates the powering of ANN-BUS devices from an auxiliary power supply such as
the FCPS-24S6/8, when the maximum number of ANN-BUS devices exceeds the ANN-BUS
power requirements.
FCPS-24S6/8
36
FACP
TB3
Primary ANN-BUS
Figure 2.16 FACP wiring to ANN-BUS Device
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)
TB3
-24 VDC
+24 VDC
ANN-BUS and power wiring are
supervised and power-limited
Figure 2.17 Powering ANN-BUS Devices from FCPS-24S6/8
ANN-BUS and power wiring are
supervised and power-limited
N-ANN-80
FACP
Primary ANN-BUS
ANN-BUS
N-ANN-80
RP-2001 Series Manual — P/N 52985:D5 1/26/2017
ANN-BUS Devices