Advanced Programming Parameters (5 - Cycle Softener System) - Pentair AUTOTROL MAGNUM 293 Installer Manual

Table of Contents

Advertisement

6.4.2

Advanced programming parameters (5 - Cycle softener system)

Parameter
description
P9 Units of measure
P10
Clock mode
P11 Service interval
P12
Remote
regeneration
P13
Chlorine
generator
options
P14
Refill rate
P15
Draw rate
P16
Reserve type
P17 Initial average or
fixed reserve
P18
Flow sensor
select
P19 K-factor or pulse
equivalent
* Default value selected with valve type and resin volume.
** Factory default value is "0" for North America and "1" for World units.
Ref. MKT-IM-012 / D - 03.02.2022
Installer manual Autotrol Magnum 293 - 298 Logix 742-762 - Programming
Range of
Default
values
value
0 - 1
**
0 - 1
**
0 - 250
0
3 - 250
0
0 - 2
0
1 - 700
*
1 - 700
*
0 - 3
0
0 - 70
30
0 - 5
*
1.00 -99.99
0.01
0 - 9999
1
Units of
measure
N/A
0 = US unit.
1= Metric unit.
N/A
0 = 12 hours clock.
1 = 24 hours clock.
Months
Uses 30 days for each month.
Months
Time remote switch must be
active to start regeneration on
742 controller.
N/A
0 = no chlorine generator.
1= salt check only.
2 = generate chlorine.
gpm x 100
-
gpm x 100
-
N/A
0 = variable reserve delayed
regeneration.
1 = fixed reserve delayed
regeneration.
2 = variable reserve immediate
regeneration.
3 = fixed reserve immediate
regeneration.
% of capacity Depends on value selected for
P16.
N/A
0 = internal Magnum NHWB.
1 = 1" Autotrol turbine.
2 = 2" Autotrol turbine.
3 = User defined.
K-factor,
4 = User defined pulse
equivalent.
5 = internal Magnum HWB.
N/A
K-factor P18 = 3.
Pulse equivalent P18 = 4.
Notes
57 / 110

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents