Basic Programming; Basic Programming Mode Chart 742-762/298 Valve Type - Pentair AUTOTROL MAGNUM 293 Installer Manual

Table of Contents

Advertisement

6.3

Basic programming

Info
Menus are displayed in a defined and incremental order.
6.3.1

Basic programming mode chart 742-762/298 valve type

Parameter
description
Program valve
type
Magnum series
Program system
size
Time setting
1:00 - 12:59 AM
0:00 - 23:59 PM
Day of week
Regeneration time 1:00 - 12:59 AM
0:00 - 23:59 PM
Days override (762
controller only)
Days between
regeneration (742
controller only)
Amount of brine
used per
regeneration
Estimated system
capacity
Hardness (762
controller only)
Ref. MKT-IM-012 / D - 03.02.2022
Range of
Default
values
value
255, 263, 268,
None
278 and
5 - 100 / F
None
12:00 PM
N/A
None
2:00 AM
0.5 - 99
0
0.5 - 99
0
50-290
110
N/A
None
30 - 2000
250
Installer manual Autotrol Magnum 293 - 298 Logix 742-762 - Programming
Units of
measure
N/A
-
liters
-
hour:
-
minute
N/A
-
hour:
-
minute
day
0 = no days override.
0.5 = regeneration twice a day at
time of regeneration and 12 hours
later.
day
0 = no days between regeneration.
0.5 = regeneration twice a day at
time of regeneration and 12 hours
later.
g/l
-
kg
For information purpose only on
the 742 controller.
equivalent
CACO
3
Mg/l
-
equivalent
CACO
3
Notes
49 / 110