U U P P S S e e n n v v i i r r o o n n m m e e n n t t a a l l s s p p e e c c i i f f i i c c a a t t i i o o n n s s
Table 25. UPS environmental specifications
Acoustic noise at 1 m
Rear exhaust
Top exhaust
Temperature range, operation
Eaton 93PM G2 xxx(200) and 93PM G2 xxx(300)
models
Recommended range *
Temperature range, operation
Eaton 93PM G2 xxx(240) and 93PM G2 xxx(360)
models
Recommended range *
Temperature range, storage and transportation
Relative Humidity
Recommended range *
Condensation
Maximum rate of temperature change **
Operating altitude
Over voltage category
Pollution degree
* ) For maximum lifetime for UPS and batteries, keep the environment in the recommended range.
** ) Limit based on ASHRAE 90.1-2013. Rapidly increasing temperature may cause condensation on
colder surfaces.
For more technical details please refer to the technical specification of the 93PM G2.
EATON 93PM G2 UPS
USER'S AND INSTALLATION GUIDE
2006/66/EC on batteries and accumulators and waste batteries and
accumulators
94/62/EC on packaging and packaging waste
74 dB(A)
77 dB(A)
+5 °C ... +40 °C
+20 °C ... +25 °C
+5 °C ... +35 °C
+20 °C ... +25 °C
-25 °C ... +55 °C
5 % - 95 %
20 % - 60%
No condensation allowed
1.67 °C / 5min
1000 m without derating
Up to 2000 m with 1% derating per each additional
100 m above 1000 m
OVC III
PD 2
P-164000956 - February 2021