50 -360 kva
Hide thumbs Also See for 93PM G2:

Advertisement

3 3 . . 9 9
B B a a s s i i c c s s y y s s t t e e m m c c o o n n f f i i g g u u r r a a t t i i o o n n s s
U U P P S S p p o o w w e e r r r r a a t t i i n n g g
The maximum attainable UPS system power rating is determined by the size of the UPS cabinet frame.
The number of UPM power modules determines the nominal power rating of the UPS. If upgradeability is
required, the UPS frame size should be chosen according to the future maximum load rating, and the
number of UPMs is chosen according to the capacity requirements on day one.
The following UPS configurations with different frame sizes and number of UPMs are possible.
Table 2. UPS configurations
Frame
Power rating
200 kW
50-200 kW
300 kW
50-300 kW
240 kVA
60-240 kVA
360 kVA
60-360 kVA
The UPS frames can be connected in parallel to create even larger systems. A maximum of eight UPSs
can be connected in parallel.
U U P P S S o o p p t t i i o o n n s s a a n n d d a a c c c c e e s s s s o o r r i i e e s s
The following table shows different standard and optional UPS features.
Table 3. Standard and optional UPS features
Feature
Touch screen display
Battery start
Integrated backfeed protection
Static bypass protective fuses
Internal maintenance bypass switch (MBS)
Battery breaker for external batteries
Sync control interface
Top air exhaust kit
Parallel cable kit
Single feed kit
EATON 93PM G2 UPS
USER'S AND INSTALLATION GUIDE
Static switch rating
# of power
modules
200 kW
1-4
300 kW
1-6
240 kVA
1-4
360 kVA
1-6
200/240 kVA frame
P-164000956 - February 2021
Power module
rating
50 kW
60 kVA
Frame
X
X
X
X
O
O
O
O
O
O
www.eaton.eu
Output power
factor
1.0
0.9
300/360 kVA frame
X
X
X
X
O
O
O
O
O
2 2 9 9