The display consists of the following parts:
1. Status bar. The status bar displays the UPS name, state, current date and time, meters information,
and a sign in/out button. It also shows any active alarms and warnings.
2. Main navigation. Select a screen by tapping on its name.
3. Content area. This is the main area for showing information on the UPS status and operations.
4. Status indicators. See Section
7 7 . . 2 2 . . 2 2
S S t t a a t t u u s s i i n n d d i i c c a a t t o o r r s s
The four symbols below the display are status indicators. They are colored light emitting diode (LED)
lamps, and they work in conjunction with the alarm horn to let you know the operating status of the UPS.
Table 17. Status indicators
Indicator
Green symbol for normal
operation
Yellow symbol for battery
mode
Yellow symbol for bypass
mode
Red symbol for active alarm
7 7 . . 2 2 . . 2 2 . . 1 1
U U P P S S d d o o o o r r c c o o l l o o r r L L E E D D i i n n d d i i c c a a t t o o r r
The LED indicators consist of two rows of LEDs located on the left and right sides of the UPS cabinet
door. The LEDs are red, green and yellow (RGY). The color of the LED is used to indicate the condition of
the UPS. The most urgent condition is always the one shown. Only one color is shown at a time. The table
below defines which color is shown.
EATON 93PM G2 UPS
USER'S AND INSTALLATION GUIDE
Status indicators.
7.2.2
Status
Description
On
The UPS is operating normally and supplying power to
the critical load.
Off
The UPS is turned off.
On
The UPS is in the battery mode. Because the battery
mode is a normal condition of the UPS, the green
indicator for normal operation also remains illuminated.
On
The UPS is in the bypass mode. The critical load is
supported by the bypass source. The green indicator for
normal operation is not illuminated when the system is in
the bypass mode.
On
The UPS has an active alarm and requires immediate
attention. The screen shows the highest priority active
alarms. All alarms are accompanied by an audible horn.
To silence the horn, press any control panel button once.
The alarm indicator may be illuminated along with other
indicators.