Eaton 93PM G2 User And Installation Manual page 39

50 -360 kva
Hide thumbs Also See for 93PM G2:

Advertisement

UPS CTO models
93PM G2 xxx(180) 0.9
pF
93PM G2 xxx(250)
93PM G2 xxx(300) 0.9
pF
UPS power upgrading is possible only if the sizing of the external cables is sufficient. Alternatively,
NOTE:
the external cabling must be upgraded as well. Fuses are of the type gG.
Cable sizing is based on the standard IEC 60364-5-52 table B.52.2 and IEC 60364-5-54 table B.54.2.
Sizing is for 70 ºC rated copper cables.
Table 11. Rated and maximum currents for each 200kW/240kVA model configuration for rated power and
voltage, rectifier input and UPS output / bypass
UPS standard models
93PM G2 xxx(200)
93PM G2 xxx(240) 0.9
pF
UPS CTO models
93PM G2 xxx(100)
93PM G2 xxx(120) 0.9
pF
93PM G2 xxx(150) 0.9
pF
93PM G2 xxx(180) 0.9
pF
EATON 93PM G2 UPS
USER'S AND INSTALLATION GUIDE
Battery cable, pos. & neg.
line [mm
2
]
2 x 95 per pole
2 x 120 per pole
2 x 150 per pole
Rated voltage [V]
Rated current [A]
380
400
415
380
400
415
Rated voltage [V]
Rated current [A]
380
400
415
380
400
415
380
400
415
380
Battery PE cable
95
120
150
Rectifier input
Maximum current [A]
361
384
343
384
331
384
374
384
371
384
358
384
Rectifier input
Maximum current [A]
181
192
172
192
166
192
187
192
186
192
179
192
260
288
258
288
248
288
281
288
P-164000956 - February 2021
Battery fuse [A]
630
700
800
UPS output / bypass
Rated current [A]
304
289
278
365
346
334
UPS output / bypass
Rated current [A]
152
144
139
182
173
167
228
217
209
273
www.eaton.eu