Eaton 93PM G2 User And Installation Manual page 38

50 -360 kva
Hide thumbs Also See for 93PM G2:

Advertisement

UPS CTO models
93PM G2 xxx(180) 0.9
pF
93PM G2 xxx(250)
93PM G2 xxx(300) 0.9
pF
Table 9. Minimum required short circuit current ratings for AC source and battery supply
UPS model
93PM G2 xxx(yyy)
Table 10. Minimum recommended multi-core cable and fuse sizes for battery connection
UPS standard models
93PM G2 xxx(200)
93PM G2 xxx(240) 0.9
pF
93PM G2 xxx(300)
93PM G2 xxx(360) 0.9
pF
UPS CTO models
93PM G2 xxx(100)
93PM G2 xxx(120) 0.9
pF
93PM G2 xxx(150)
EATON 93PM G2 UPS
USER'S AND INSTALLATION GUIDE
Phase cables [mm
185
2 x 120
2 x 185
Make sure that prospective short-circuit current resulting at the input terminals
of the UPS is equal or less than conditional short-circuit current declared on the
type plate (and technical specification) of the UPS. Also make sure that the
prospective short-circuit current meets the minimum requirements listed in
Table
Minimum required short circuit current ratings for AC source and battery
9:
supply.
Minimum short circuit current, AC ports
Battery cable, pos. & neg.
line [mm
2
]
2 x 95 per pole
2 x 95 per pole
2 x 150 per pole
2 x 185 per pole
Battery cable, pos. & neg.
line [mm
2
]
95
150
185
Rectifier, bypass and
maintenance bypass input
2
]
fuse [A]
315
500
630
CAUTION
[kA]
4
Battery PE cable
95
95
150
185
Battery PE cable
50
95
95
P-164000956 - February 2021
PE cable [mm
95
120
185
Minimum short circuit current, battery
port [kA]
4
Battery fuse [A]
630
630
800
1000
Battery fuse [A]
315
400
500
www.eaton.eu