Download Print this page

Eaton 93PM G2 User And Installation Manual page 27

50 -360 kva
Hide thumbs Also See for 93PM G2:

Advertisement

3 3 . . 5 5 . . 2 2
P P o o w w e e r r M M a a n n a a g g e e m m e e n n t t S S o o f f t t w w a a r r e e
Intelligent Power software products offer tools for monitoring and managing power devices across the
network. See Section
3 3 . . 5 5 . . 3 3
A A u u t t o o m m a a t t i i c c U U P P M M F F W W u u p p d d a a t t e e
The UPS automatically updates the firmware of the UPM plugged in a live system. The UPM FW will be
updated to the same version that all the other UPMs in the UPS use.
3 3 . . 5 5 . . 4 4
A A u u t t o o m m a a t t i i c c U U P P S S o o u u t t p p u u t t p p o o w w e e r r c c o o n n f f i i g g u u r r a a t t i i o o n n
The UPS automatically calculates the output power capacity based on the number of UPMs connected to
the device.
3 3 . . 6 6
O O p p t t i i o o n n s s a a n n d d a a c c c c e e s s s s o o r r i i e e s s
Contact your Eaton sales representative for more information about the available options and
accessories.
3 3 . . 6 6 . . 1 1
M M a a i i n n t t e e n n a a n n c c e e B B y y p p a a s s s s S S w w i i t t c c h h
The Maintenance Bypass Switch (MBS) enables power to completely bypass and isolate the UPS so that
the UPS can be safely serviced without interrupting power to critical systems.
The MBS is available internally as an option for 200 kW/240 kVA frames or in an external enclosure as an
accessory item.
3 3 . . 6 6 . . 2 2
T T o o p p a a i i r r e e x x h h a a u u s s t t k k i i t t
The top air exhaust kit is used to direct the UPS cooling air front-to-top. The kit will eliminate the cooling
clearance requirement from the back of the unit, and enable installing the UPS even against a wall, in a
corner or back-to-back.
Refer to Section
Site preparations for further information.
4.4
3 3 . . 6 6 . . 3 3
S S i i n n g g l l e e f f e e e e d d k k i i t t
The Eaton 93PM G2 UPS is configured for dual feed by standard, requiring a separate feed for rectifier
and static bypass input. Single feed kit is available both as factory installed or on-site installed option.
3 3 . . 6 6 . . 4 4
I I n n t t e e r r n n a a l l b b a a t t t t e e r r y y b b r r e e a a k k e e r r
The internal battery breaker disconnects the DC supply to the UPS so that the UPS can be safely
serviced.
3 3 . . 7 7
U U P P M M i i n n s s t t a a l l l l a a t t i i o o n n a a n n d d r r e e p p l l a a c c e e m m e e n n t t
A new UPM can be installed in the cabinet any time in the future when power needs change. This enables
the UPS system to grow with the business, thus lowering the initial investment required for the system on
day one.
For a listing of the upgradeable configurations, see Table
EATON 93PM G2 UPS
USER'S AND INSTALLATION GUIDE
About communication interfaces for more information.
6.1
UPS configurations.
2:
P-164000956 - February 2021