Action
LAN drops are installed.
All LAN connections are completed.
Air conditioning equipment is installed and operating correctly.
There is sufficient workspace around the UPS and other cabinets.
Sufficient lighting is provided around all the UPS equipment.
A 230 VAC service outlet is located within 7.5 meters of the UPS equipment.
The Remote Emergency Power-off (REPO) device is properly mounted and its
wiring is connected inside the UPS cabinet.
If EPO is used in the NC configuration, a jumper is installed on the UPS EPO
terminals between pins 1 and 2.
(OPTIONAL) Alarm relays and signal outputs are wired appropriately.
(OPTIONAL) A remote battery disconnect control is properly mounted and its
wiring is terminated inside the UPS and battery cabinet.
(OPTIONAL) Accessories are properly mounted and their wiring is terminated
inside the UPS cabinet.
Start-up and operational checks are performed by an authorized Eaton Customer
Service Engineer.
4 4 . . 4 4
S S i i t t e e p p r r e e p p a a r r a a t t i i o o n n s s
For the UPS system to operate at peak efficiency, the installation site must meet the environmental
parameters outlined in these instructions. If the UPS needs to be operated at an altitude higher than 1,000
m, contact your service representative for important information about high altitude operation. The
operating environment must meet the height, clearance, and environmental requirements specified.
4 4 . . 4 4 . . 1 1
E E n n v v i i r r o o n n m m e e n n t t a a l l c c o o n n s s i i d d e e r r a a t t i i o o n n s s
Install the UPS to a temperature and humidity controlled indoor area, free of conductive contaminants. Do
not expose the UPS to direct sunlight or install it near a heat source. The environmental requirements
specified in Section
9.3
and are the maximum, not to exceed, ratings.
Do not expose the UPS for overly aggressive environments, like salt mist or corrosive gases. High
relative humidity accelerates the effects of contaminants. The UPS should be installed in a G1
environment (based on ANSI/ISA S-71.04 classifications). If the UPS is used in a more aggressive
environment, it can cause reduced product life and possibly early failure. If the installation location
does not meet the recommended environment, contact Eaton service representative for further
information.
Do not place the UPS near a source of dust or sand. Excessive amount of dust or sand can cause
damage or lead to malfunction.
EATON 93PM G2 UPS
USER'S AND INSTALLATION GUIDE
UPS environmental specifications are for the air at the intake ports of the UPS,
P-164000956 - February 2021