UPS maintenance
8 8 . . 1 1
I I n n t t r r o o d d u u c c t t i i o o n n t t o o U U P P S S m m a a i i n n t t e e n n a a n n c c e e
The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and
assemblies are located for easy removal with very little disassembly. This design allows authorized
service personnel to perform routine maintenance and servicing quickly. Schedule periodic performance
checks of your UPS system to keep it running properly. Regular routine checks of the operation and
system parameters enable your system to function efficiently for many trouble-free years.
8 8 . . 2 2
I I m m p p o o r r t t a a n n t t s s a a f f e e t t y y i i n n s s t t r r u u c c t t i i o o n n s s
Remember that your UPS system is designed to supply power EVEN WHEN IT IS DISCONNECTED
FROM THE UTILITY POWER. The UPS module interiors are unsafe until the DC power source is
disconnected and the electrolytic capacitors are discharged.
After disconnecting the utility power and the DC power, authorized service personnel must wait at least 5
minutes for capacitor bleed-off before attempting internal access to the UPS module.
EATON 93PM G2 UPS
USER'S AND INSTALLATION GUIDE
LETHAL VOLTAGE. Do not operate the UPS system without the cabinet doors
or protective panels secured. Do not make any assumptions about the electrical
state of any cabinet in the UPS system.
All service and maintenance work must be done only by service personnel
qualified and authorized by Eaton.
A warning label, shown in Figure
input terminals and all the primary power isolators used to isolate the UPS unit if
the UPS is connected to an IT earthed supply, or if the UPS input is connected
through external isolators that, when opened, isolate the neutral. You can get
these warning labels from your local service representative.
DANGER
WARNING
CAUTION
Warning label, must be installed at the UPS
44:
P-164000956 - February 2021