Eaton 93PM G2 User And Installation Manual page 35

50 -360 kva
Hide thumbs Also See for 93PM G2:

Advertisement

Figure 11. 93PM G2 UPS top dimensions, with top-air exhaust option
The UPS cabinets use forced air cooling to regulate internal component temperature. By standard, air
inlets are in the front of the cabinet and outlets are in the back. You must allow clearance in front of and
behind each cabinet for proper air circulation.
With the optional top air exhaust kit, it is possible to configure the air outlets in the top rear of the cabinet.
With this option, the UPS can be installed against a wall or back-to-back.
The clearances required around the UPS cabinet in both of these situations are shown in Table
cabinet clearances.
Table 6. UPS cabinet clearances
From the top of the cabinet
From the front of the cabinet
From the back of the cabinet
From the side of the cabinet
*) 0 mm if top air exhaust kit installed
Figure 12. 93PM G2 UPS cabinet clearances
Z
= clearance at the
back
EATON 93PM G2 UPS
USER'S AND INSTALLATION GUIDE
Eaton 93PM G2 xxx(200) and 93PM
G2 xxx(300) models
400 mm
1000 mm
200 mm*
0 mm
Y
= clearance at the top X
Eaton 93PM G2 xxx(240) and 93PM
G2 xxx(360) models
500 mm
1000 mm
300 mm*
0 mm
= clearance at the front
P-164000956 - February 2021
UPS
6: