Download Print this page

Eaton 93PM G2 User And Installation Manual page 82

50 -360 kva
Hide thumbs Also See for 93PM G2:

Advertisement

1. Follow the normal start position:
Figure 40. Normal positions of the switches
A
Bypass input
B
Rectifier input
C
UPS output
2. Do the transfer from the double conversion mode to the bypass mode as instructed in Section
Transfer from the double conversion mode to the bypass mode. Remember to verify the transfer
7.4.4
before proceeding to the next step.
3. Open the UPS door.
4. Turn on the maintenance bypass switch (MBS) S2. This connects the feed from the bypass input to the
UPS output.
5. Turn off the bypass input switch (BIS) S1. This disconnects the feed for the static bypass module.
6. Do the LOAD OFF procedure as described in Section
7. Open the incoming feeder to disconnect the power from rectifier input terminals X1.
8. Open all battery breakers feeding the UPS battery input terminals X4.
The UPS is now in the maintenance bypass mode:
EATON 93PM G2 UPS
USER'S AND INSTALLATION GUIDE
1
Bypass input switch (BIS) S1
2
Maintenance bypass switch (MBS) S2
De-energize the critical load.
7.4.10
P-164000956 - February 2021