Eaton 93PM G2 User And Installation Manual page 52

50 -360 kva
Hide thumbs Also See for 93PM G2:

Advertisement

Cable entry to the UPS is always on the top, the bottom or the rear of the cabinet.
Follow the installation instructions given in Section
NOTE:
The frame of the external battery cabinet must be grounded to the UPS. If the distance between the
NOTE:
UPS and external battery cabinet is less than 500 mm, a separate EMI grounding between the two
cabinets is needed. The shipping/fixing bracket mounted to the front side of the UPS has two alternative
grounding cable fixing points for this purpose. See Figure
cabinet. Other end of the cable is connected to the closest available point in the chassis of the external
battery cabinet. The connection point must be unpainted, and provide reliable mechanical and electrical
contact to the chassis. For the cable size, refer to Table
fuse sizes for battery connection.
Figure 19. EMI grounding point to external battery cabinet
1. EMI grounding points
5 5 . . 5 5
I I n n s s t t a a l l l l a a r r e e m m o o t t e e E E P P O O s s w w i i t t c c h h
You can use a remote EPO switch in case of an emergency to shut down the UPS and remove power to
the critical load from a location away from where the UPS is installed.
EPO is connected to the UPS's top front panel, on connector EPO. Figure
switch shows the NO and NC connections of the EPO switch.
EPO connector (front view):
A = Normally open
B = Normally closed
EATON 93PM G2 UPS
USER'S AND INSTALLATION GUIDE
UPS system power wiring preparations.
4.4.3
EMI grounding point to external battery
19:
Minimum recommended multi-core cable and
10:
20:
P-164000956 - February 2021
Connections of the EPO
www.eaton.eu