Expansion Valve; Checking Procedures - Daikin Sky Air Advance RZA200D7Y1B Service Manual

Hide thumbs Also See for Sky Air Advance RZA200D7Y1B:
Table of Contents

Advertisement

3
|
Components

3.4 Expansion valve

3.4.1 Checking procedures

To perform a mechanical check of the expansion valve
To perform an electrical check of the expansion valve
Service manual
68
Is the problem solved?
Yes
No
INFORMATION
It is recommended to perform the checks in the listed order.
Prerequisite: Power OFF the unit for 3 minutes. Then turn ON the unit and listen to
the expansion valve assembly. If the expansion valve does NOT make a latching
sound, continue with the electrical check of the expansion valve, see
"3.4.1 Checking
procedures" [
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Remove the expansion valve coil from the expansion valve body, see
"3.4.2 Repair
procedures" [
INFORMATION
After the check, remove the magnet from the expansion valve body and install the
expansion valve coil on the expansion valve body. Make sure that the expansion
valve coil is firmly slid onto the expansion valve body.
2 Slide the expansion valve magnet over the expansion valve body and gently
rotate the magnet clockwise/counterclockwise to manually close/open the
expansion valve.
Does the expansion valve open?
Yes
No
1 First perform a mechanical check of the expansion valve, see
4
procedures" [
 68].
2 Disconnect the electrical connector of the expansion valve coil from the
appropriate PCB and measure the resistance of all windings (between the pins
of each phase (wire) and the common wire) using a multi meter. All
measurements MUST be approximately the same.
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4
 68].
"3.12 Plate
4
 70].
Action
Perform an electrical check of the
expansion valve, see
procedures" [
Replace the expansion valve body, see
"3.4.2 Repair
4
work" [
 111].
"3.4.1 Checking
4
 68].
4
procedures" [
 70].