4.1.2 Repair procedures
To adjust the power supply
To correct the wiring between PCB's
4.2 Refrigerant circuit
4.2.1 Checking procedures
To check if the stop valves are open
RZA200+250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
1 Make sure that the power source is in line with the requirements described in
the databook.
2 Adjust the power supply within 50 Hz ± 3%.
Is the problem solved?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Make sure that all wires are firmly and correctly connected, see
diagram" [
4
151].
2 Check the continuity of all wires.
3 Replace any damaged or broken wires.
Is the problem solved?
Yes
No
INFORMATION
It is recommended to perform the checks in the listed order.
Prerequisite: Remove the required plate work, see
1 Remove the caps.
4
Third party components
|
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
"3.12 Plate
work" [
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
"3.12 Plate
work" [
4
111].
"6.2 Wiring
4
111].