6
|
Technical data
Mode 2: Field settings
In mode 2 you can make field settings to configure the system.
Make sure to perform a power reset via the outdoor unit after changing the field settings.
(
)
*
This column shows the number of times you have to push the SET button (BS2) to access the field setting.
(
)
**
The bold content is the default setting.
(
)
N°
*
0
Night time low noise setting
1
Capacity priority setting
2
Capacity up setting
3
Low noise setting (see diagram
below)
(low noise level, start and end time
of automatic low noise during
nighttime)
7
Defrost slow starting setting
8
Defrost quick starting setting
17
Refrigerant recovery mode setting
(vacuum mode field setting)
18
Power transistor check mode
settings
56
Drain pan heater ON time after
defrost operation
79
High external‑static‑pressure‑mode
setting
Service manual
174
Item
Display
2.00
1
Off
2
On
2.01
1
Off
2
On
2.02
1
Off
2
On
2.03
1
Level 1, 22h00~6h00
2
Level 1, 22h00, 8hhh00
3
Level 2, 22h00, 6h00
4
Level 2, 22h00, 8hhh00
5
Level 2, 20h00~8h00
6
Level 3, 22h00, 8h00
7
Level 3, 20h00, 8h00
2.07
1
Off
2
On
2.08
1
Off
2
On
2.17
1
Off
2
On
2.18
1
Off
2
On
2.56
1
1 min
2
5 min
3
10 min
4
15 min
5
25 min
6
30 min
7
45 min
2.79
1
Enabled
2
Disabled
3
Re‑judgement disabled
(
)
Content
**
RZA200+250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05