To remove the solenoid valve body
RZA200+250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
Prerequisite: If needed, remove any parts or insulation to create more space for
the removal.
1 Remove the screws that fix the solenoid valve to the bracket.
a
Screw
b
Solenoid valve coil
c
Bracket
d
Screw
e
Solenoid valve body
2 Remove the screw that fixes the solenoid valve coil to the solenoid valve body.
3 Remove the solenoid valve coil from the solenoid valve body.
4 Disconnect the solenoid valve connector from the main PCB.
5 Cut all tie straps that fix the solenoid valve harness.
6 To install the solenoid valve coil, see
Prerequisite: Recuperate the refrigerant from the refrigerant circuit, see
"4.2.2 Repair
procedures" [
Prerequisite: If needed, remove any parts or insulation to create more space for
the removal.
1 Remove the solenoid valve coil, see
2 Cut the solenoid valve body pipes using a pipe cutter.
c
a
d
b
e
"3.14.2 Repair