Daikin Sky Air Advance RZA200D7Y1B Service Manual page 127

Hide thumbs Also See for Sky Air Advance RZA200D7Y1B:
Table of Contents

Advertisement

To install the solenoid valve coil
RZA200+250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
CAUTION
Overheating the valve will damage or destroy it.
4 After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
5 To install the solenoid valve coil, see
6 Add
refrigerant
4
procedures" [
 142].
1 Install the solenoid valve coil on the solenoid valve body.
a
Screw
b
Solenoid valve coil
c
Bracket
d
Screw
e
Solenoid valve body
2 Install and tighten the screw to fix the solenoid valve coil to the solenoid valve
body.
3 Install and tighten the screws to fix the solenoid valve to the bracket.
4 Route the solenoid valve harness towards the switch box.
5 Connect the solenoid valve connector to the main PCB.
WARNING
When reconnecting a connector to the PCB, do NOT apply force, as this may damage
the connector or connector pins of the PCB.
6 Fix the solenoid valve harness using new tie straps.
INFORMATION
Replace all cable ties that were cut during removal.
Is the problem solved?
Yes
"3.14.2 Repair
to
the
refrigerant
c
a
d
b
e
Action
No further actions required.
3
Components
|
4
procedures" [
 124].
circuit,
see
"4.2.2  Repair
Service manual
127

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sky air advance rza250d7y1b

Table of Contents