Daikin Sky Air Advance RZA200D7Y1B Service Manual page 63

Hide thumbs Also See for Sky Air Advance RZA200D7Y1B:
Table of Contents

Advertisement

To install the compressor
RZA200+250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
6 Remove the 3 dampers from the compressor.
INFORMATION
The compressor dampers may look different.
7 Remove the bushings and keep them for re-use.
8 To install the compressor, see
1 Check the state of the dampers. Replace if worn.
2 Install the 3 dampers in the correct location on the unit.
a
c
a
Nut
b
Compressor
c
Damper
INFORMATION
The compressor dampers may look different.
3 Remove the caps from the compression pipe and suction pipe.
CAUTION
The oil in the compressor is hygroscopic. Therefore remove the caps from the
compressor pipes as late as possible.
4 Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
5 Wrap a wet rag around the compressor pipes and solder the compressor pipes
to the refrigerant pipes.
"3.2.2 Repair
procedures" [
b
a
c
a
c
3
Components
|
4
 61].
Service manual