Samson TROVIS 3730-3 Mounting And Operating Instructions page 173

Smart positioner (hart)
Hide thumbs Also See for TROVIS 3730-3:
Table of Contents

Advertisement

Menu
Rated travel not
achieved
No movement
Pin position
Canceled (control
accuracy)
Low control
accuracy
Positioner not
initialized
Initialization
canceled (external)
EB 8484-3 EN
10.1.1.8
Recommended action: Check positioner attachment, pin position and supply
10.1.1.9
10.1.1.10
Recommended action: Check positioner mounting, pin position and supply air.
10.1.1.11
10.1.1.12
Recommended action: Check pin position.
10.1.1.13
10.1.1.14
Recommended action: Check positioner attachment, pin position and supply
10.1.1.15
10.1.1.16
Recommended action: Check positioner attachment, pin position and supply
10.1.1.17
10.1.1.18
Recommended action: Perform an initialization.
10.1.1.19
Recommended action: Check power supply/electrical signal. Re-initialize the
10.1.1.20
Annex A (configuration instructions)
Adjustment range/values [default setting]/description
The detected rated travel is smaller than the value in the
setting.
pressure.
Confirm to clear message.
Possible cause: valve blockage.
Check piping and configuration of the mounting parts.
Move the positioner out of the fail-safe position.
Confirm to clear message.
The adjusted lever M does not match the rated travel.
Confirm to clear message.
Control criteria are not fulfilled.
air. Re-initialize the positioner. Possibly use a screw
restriction.
Confirm to clear message.
Control criteria are not fulfilled.
air. Re-initialize the positioner. Possibly use a screw
restriction.
Confirm to clear message.
The positioner needs to be initialized.
Initialization was canceled, e.g. due to forced venting
or IP shutdown.
positioner.
Confirm to clear message.