Samson TROVIS 3730-3 Mounting And Operating Instructions page 165

Smart positioner (hart)
Hide thumbs Also See for TROVIS 3730-3:
Table of Contents

Advertisement

Menu
Upper end position
End position w >= (set
point cutoff increase)
Identification
Positioner
Firmware version
Hardware version
Serial number
HART
communication
®
Non-conducting
Fixed value
(communication)
Fixed value
(communication)
Polling address
Loop current value
Tag no.
Description
Tag no. (long)
Preambles
Find device flag
Final assembly number
Control parameters
EB 8484-3 EN
Adjustment range/values [default setting]/description
8.1.11
[Deactivated]/Activated
51.0 to 100.0 % [99.0 %]
8.1.12
If the set point w reaches up to the entered percentage at the
final value that causes the valve to open, the actuator is
immediately filled with air (with AIR TO OPEN) or completely
vented (with AIR TO CLOSE). This action always lead to the
valve being completely opened.
Example: set the cutoff to 99 % for three-way valves.
8.2
8.2.1
8.2.1.1
Indicates firmware version.
8.2.1.2
Indicates the hardware version.
8.2.1.3
Indicates serial number.
8.3
Yes/[No]
8.3.1
8.3.2
Active/[Not active]
8.3.3
1.0 to [100.0 %]
8.3.4
[0] to 63
8.3.5
0/1
Entry of max. 8 characters
8.3.6
8.3.7
Entry of max. 16 characters
8.3.8
Entry of max. 32 characters
8.3.9
[5] to 20
Yes/[No]
8.3.10
8.3.11
Read only
8.4
Annex A (configuration instructions)
16-7