Start-up and configuration
7.4 Start-up menu
1. Press
(in start screen) to change to the main menu.
until Start-up [7] appears.
2. Turn
3. Press
to go to the Start-up menu.
7.4.1
Setting the actuator type
Three different parameters are available for selection:
− Linear actuator
− Rotary actuator
− Linear actuator (expert) with separate setting options for pin position and nominal range
(within Start-up [7] menu) until Actuator [7.1] appears.
1. Turn
2. Press and turn
3. Press
to confirm the setting.
7.4.2
Determining the fail-safe position
Define the fail-safe position of the valve taking the valve type and the actuator's direction of
action into account. Position the AIR TO OPEN/AIR TO CLOSE slide switch accordingly:
Fail-safe position
Switch setting: AIR TO OPEN
Switch setting: AIR TO CLOSE
For checking purposes: after initialization is completed, the positioner display must read 0 %
when the valve is closed. If this is not the case, change the slide switch position and re-initial-
ize the positioner.
7-4
to set the actuator type.
Description
Signal pressure opens the valve, e.g. for a fail-
close valve
Signal pressure closes the valve, e.g. for a fail-
open valve
EB 8484-3 EN