Annex A (configuration instructions)
Menu
Manual set point (MAN)
Reason for fail-safe
position
Change reading direction 5
User level
Start-up
Actuator
Pin position
Pin position for linear
actuator
Pin position for rotary
actuator
Pin position for linear
actuator (expert)
Nominal range
Nominal range for linear
actuator
16-2
Adjustment range/values [default setting]/description
3
–25.0 to 125.0 % [0.0 %]
Adjust the manual set point with the rotary pushbutton. The
current travel/angle is displayed in % when the positioner is
initialized. If the positioner is not initialized, the position of the
lever in relation to the longitudinal axis is indicated in degrees
(°).
4
Reason for change to fail-safe position displayed. The
parameter is only displayed in the event of a change to the
fail-safe position.
Reading di-
rection
The reading direction of the display is turned by 180°.
[On-site (read only)]/On-site
6
The option to change data is unlocked (revoked if no settings
are entered within five minutes).
7
7.1
[Linear actuator]
Rotary actuator
Linear actuator (expert)
Select type of actuator: linear actuator (expert) with separate
setting options for pin position and nominal range.
Follower pin must be mounted in the proper position
depending on the valve travel/opening angle (see travel tables
in the 'Installation' section).
7.2
[None]/17/25/35/50/70/100/200/300 mm
90°
7.3
[10] to 655 mm
7.4
The pin position is continuously adjustable within the specified
range.
The possible adjustment range depends on the selected pin
position. If no pin position has been entered, 'Nominal range'
is only available for the 'Linear actuator (expert)' actuator type
(see travel tables in the 'Installation' section).
7.5
60.0 to 300.0 [200.0]
EB 8484-3 EN