Operation
Table 8-2: Reset function
Reset function
Reset diagnosis
Reset (standard)
Reset (advanced)
Restart
Reset initialization
8-6
Description
Resets all diagnostic functions
including graphs and histograms.
Resets the positioner to the state as
upon delivery. Actuator and valve-
specific settings remain unchanged.
Configuration settings of the
diagnostics are reset.
All parameters will be reset to their
defaults adjusted upon delivery.
The positioner is shut down and
restarted.
All parameters for the start-up
settings are reset. The positioner
needs to be re-initialized
afterwards.
Example
Diagnosis analyses of operating
hours in the past are no longer
relevant.
The attachment situation has
changed. The valve has been
repaired or modified. The
positioner diagnosis data are no
longer relevant. The positioner must
be re-initialized.
Positioner is mounted on another
actuator/valve.
Putting the valve back into
operation after a malfunction
Changes to the start-up settings are
necessary.
EB 8484-3 EN