Lennox iComfort G71MPP-03 Setup Manual page 14

Hide thumbs Also See for iComfort G71MPP-03:
Table of Contents

Advertisement

HUMIDIFICATION SETTINGS — FEATURE SCREEN
1. From the Main Screen, press the right arrow icon to go the the Features
screen.
2. From the Features screen, select system settings.
3. Touch the button of the humidification controls you want to adjust; if it says
humidifier OFF, one touch will display a selection for ON.
4. When you touch the set-to button, the arrows appear, allowing you to change
to the desired humidity percentage setting.
SYSTEM SETTINGS
Appears only when
humidifier controls
heat pump is
present
heating
35
humidifier
mode
is ON
COMFORT
(default is ON)
Wi-Fi
9:39 am Aug 15, 2012
Figure 15. System Settings Screen (Example Only) -
Communicating Outdoor Unit
DE-HUMIDIFICATION SETTINGS — SYSTEM DEVICES SCREEN
system devices
System
Air Conditioner
Furnace
Thermostat
Humiditrol
System
3rd Stage Delay
4th Stage Delay
Lock In 2nd Stage HP by Outdoor Temp
Balance Point Control
Humiditrol Comfort Adjust
Min De-humidification Setpoint
Humiditrol Comfort Adjust
Select one
Maximum Overcooling
Minimum Overcooling
3a
save
Humiditrol Comfort Adjust settings are
only available on units equipped with
®
a Humiditrol
De-humidification
device.
507152-01
de-humidifier controls
%
%
ClimateIQ
40
setting
set to
MOD
set to
(default is DRY)
Select the humidity level
that matches your
regional weather
To adjust a setting,
highlight it,
then press Edit
System
1a
1b
De-humidification Control Mode
current value:
Midpoint Overcooling
2a
Midpoint Overcooling
back
System
Staged Delay TImers
cancel
2nd Stage Delay
3b
3rd Stage Delay
4th Stage Delay
Lock In 2nd Stage HP by Outdoor Temp
Balance Point Control
Humiditrol Comfort Adjust
Min De-humidification Setpoint
OD/Humid Boundary
Outdoor Temperature Reading Calibr
9:39 am Aug 15, 2012
Figure 16. Adjust a Communicating Device Setting — De-humidification
DISPLAY, BASIC AND PRECISION—These modes allow user
control of relative humidity between 15 and 45%. These conditions
must be met for either mode to operate:
S
humidification mode has been enabled, and
S
the unit is in HEAT mode, and
S
humidification demand exists (24V present at H), and
S
DISPLAY mode indicates humidification is OFF.
S
BASIC mode mode also requires presence of heating de
mand [Y for HP heat, or W for gas heat (W may be energized
with G de-energized)].
S
PRECISION—(Available only if Wi-Fi is operational or out
humidifier
display
door sensor is attached)
is ON
Basic Dew Point Control adjustment mode will change the humidi
(default is ON)
fication set point based on the outdoor temperature and a user-
defined dew point adjustment setting.
Precision Dew Point Control adjustment mode will operate when
these conditions are met:
?
S
humidification mode has been enabled, and
S
the unit is in HEAT mode, and
S
humidification demand exists (24V present at H).
Pre-adjustment REQUIREMENTS:
1st, the device has been installed
about
2nd, from the "Add or Remove Non-communicating equipment?", press next.
3rd, in the "Adjust a setting..." screen, configure the device as follows:
1.In the "system devices" list, use the arrows (1a) to highlight System. Press
resetAll
edit (1b).
®
2.Humiditrol
edit
ditrol Comfort Adjust. The current value defaults to Maximum Overcooling.
Press edit (2b).
®
3.Humiditrol
reinstall
ing level; press save (3b). (After saving, check that the current value now
shows the new selection).
4.Use arrows (4a) to highlight Min De-humidification Setpoint; press edit (4b).
Note the current value (e.g. 45).
reset
5.Use arrows (5a) to make changes; press save (5b). (After saving, check that
the current value now shows the new selection).
2b
edit
6.Press the back button to return to "Adjust a setting..." screen.
De-humidification Control Mode
current value:
45
4a
6
back
Page 14
How Humidification Mode Works
only—In the "System" list, use the arrows (2a) to highlight Humi
only—Touch one of the radio buttons (3a) to select the overcool
Min De-humidification
4b
Range is 40 to 60
edit
Default is 45, inc:1
set-to
42
reset
5b
save
(returns to
adjust a
setting
screen)
Setpoint
5a
cancel
7/2013