In LonWorks, the timeout function is also activated when the following SNVTs fail to be updated within the time
period specified in par.8-03
nviStartStop
nviReset Fault
nviControlWord
8-05 End-of-Timeout Function
Option:
[0]
Hold set-up
[1] *
Resume set-up
8-06 Reset Control Timeout
Option:
[0] *
Do not reset
[1]
Do reset
8-07 Diagnosis Trigger
Option:
[0] *
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
8-10 Control Profile
Option:
[0] *
FC profile
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
TR200 LonWorks
Control Timeout
Time:
Function:
Select the action after receiving a valid control word following a timeout.
This parameter is active only when par.8-04
set to [Set-up 1-4].
Retains the set-up selected in par.8-04
displays a warning, until par.8-06
the adjustable frequency drive resumes its original set-up.
Resumes the set-up active prior to the timeout.
Function:
This parameter is active only when the choice
selected in par.8-05
Retains the set-up specified in par.8-04
set-up 1-4] following a control timeout.
Returns the adjustable frequency drive to the original set-up following a
control word timeout. When the value is set to
frequency drive performs the reset and then immediately reverts to the
Do not reset
[0] setting.
Function:
This parameter has no function for LonWorks.
Function:
Select the interpretation of the control and status words corresponding
to the installed serial communication bus. Only the selections valid for
the serial communication bus installed in slot A will be visible in the
keypad display.
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
Control Timeout Function
Control Timeout Function
Reset Control Timeout
End-of-Timeout
Function.
Control Timeout
Parameters
is
and
toggles. Then
Hold set-up
[0] has been
Function, [Select
Do reset
[1], the adjustable
8-3