Trane LonWorks TR200 Instruction Manual page 37

Option module
Table of Contents

Advertisement

Configuration of the system
ECB Option Status
Variable
name:
nvoECBStatus
This variable displays the current status of the ECB option.
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
These variables are available only if the
Parameter Access Response
Variable name:
nvoParamResponse
This output variable is used for the adjustable frequency drive access.
A special UNVT has been defined for this variable.
For more information on parameter access, please refer to the
5-16
SNVT
type:
SNVT_state
Electronic Control Bypass option
State:
Boolean 1 bit x 16
Test Mode
Drive Mode
Automatic Bypass Mode
Bypass Mode
Reserved
Motor Running from Bypass/Drive
Overload Trip
M2 Contactor Fault
M3 Contactor Fault
External Interlock
Manual Bypass Override
(ECB) has been installed.
SNVT type:
UNVT_param_response
How to Access TR200 Parameters
section.
TR200 LonWorks