Trane LonWorks TR200 Instruction Manual page 28

Option module
Table of Contents

Advertisement

Analog Output (X30 / 8)
Variable
SNVT
name:
type:
nvi101AnOut1
SNVT_lev_percent
This output variable applies only if the General Purpose I/O option is installed in the adjustable frequency drive.
This variable controls the X30/8 analog output on the General Purpose I/O option 0–20 mA or 4–20 mA.
In order to control output X30/8 via LonWorks, par.6-60
options:
[139] Bus ctrl. 0–20 mA
[140] Bus crtl. 4–20 mA
[141] Bus crtl. 0–20 mA Timeout
[142] Bus crtl. 4–20 mA Timeout
Function:
Bus crtl. 0–20 mA [139]: The output is controlled via bus. In the event of bus timeout, the output level remains
unchanged.
Bus crtl. 4–20 mA [140]: The output is controlled via bus. In the event of bus timeout, the output level remains
unchanged.
Bus crtl. 0–20 mA [141]: The output is controlled via bus. In the event of bus timeout, the output level is set to
the predefined level in par.6-64
Bus crtl. 4–20 mA [142]: The output is controlled via bus. In the event of bus timeout, the output level is set to
the predefined level in par.6-64
Analog Output (X42 / 7)
Variable
SNVT
name:
type:
nvi109AnOut1
SNVT_lev_percent
Analog Output (X42 / 9)
Variable
SNVT
name:
type:
nvi109AnOut2
SNVT_lev_percent
TR200 LonWorks
Min.:
0 %
Terminal X30/8 Output
Terminal X30/8 Output Timeout
Terminal X30/8 Output Timeout
Min.:
0 %
Min.:
0 %
Configuration of the system
Value:
Max.:
100 %
must be set to one of the following
Preset.
Preset.
Value:
Max.:
100 %
Value:
Max.:
100 %
Resolution:
0.01%
Resolution:
0.01%
Resolution:
0.01%
5-7