Trane LonWorks TR200 Instruction Manual page 29

Option module
Table of Contents

Advertisement

Configuration of the system
Analog Output (X42 /11)
Variable name:
SNVT type:
nvi109AnOut3
SNVT_lev_percent
These variables contain the value allocated to the analog output terminal X42/7-11 of the
variable type is changeable with the commissioning tool.
This variable is available only if the Programmable I/O option (MCB 115) has been installed.
Setting of RTC
Variable
SNVT
name:
type:
nviTimeStamp
SNVT_time_stamp
Use this input to set the built-in Real Time Clock.
ECB Option Mode
Variable
SNVT
name:
type:
nviECBMode
SNVT_state
Controls the operation mode of the ECB option. The binary value of this variable is mapped directly into par.
31-00
Bypass
Mode.
[0] Drive
[1] Bypass
ECB Remote Bypass Activation
Variable
SNVT
name:
type:
nviECBActivation
SNVT_state
Controls the remote activation of the ECB option.
The binary value of this variable is mapped directly into par. 31-90.
[0] Disabled
[1] Enabled
This input variable applies only if the ECB option is installed in the adjustable frequency drive.
5-8
Min.:
0 %
Year
Month
2000 -3000
0 - 12
0 - 31
Boolean 1 bit x 16
Boolean 1 bit x 16
Value:
Max.:
Resolution:
100 %
Analog I/O option
Field:
Day
Hour
Minute
0 - 23
0 - 59
State:
State:
TR200 LonWorks
0.01%
. The
Second
0 - 59