Network Variable Description - Vsd Profile - Input; Network Variable Description - Vsd Profile - Output - Trane LonWorks TR200 Instruction Manual

Option module
Table of Contents

Advertisement

Configuration of the system
Configuration Properties (nci)
Variable function
Max. motor speed [%]
Min. motor speed [%]
Nom. motor speed [RPM]
Nom. motor frequency [Hz]
Min. ramp-up time [s]
Min. ramp-down time [s]
Heartbeat time [s]
A range of network configuration variables (SCPTs) is available for configuration of the adjustable frequency
drive parameters. These parameters require setting only once, usually following installation.
Please note that the settings written to configuration properties (NCIs) will be stored in the non-volatile mem-
ory. Continuous writing to configuration properties may damage the non-volatile memory.

Network Variable Description - VSD Profile - input

Adjustable Frequency Drive Speed Setpoint
Variable name:
nviDrvSpeedStpt
This input variable provides start / stop control and a speed reference.

Network Variable Description - VSD Profile - Output

Drive Speed
Variable
SNVT
name:
type:
nvoDrvSpeed
SNVT_lev_percent
This variable contains the adjustable frequency drive speed as a percentage of the nominal speed.
5-18
Variable name
nciMaxSpeed
nciMinSpeed
nciNmlSpeed
nciNmlFreq
nciRampUpTime
nciRampDownTime
nciSndHrtBt
SNVT type:
State:
SNVT_switch
0 (False)
1 (True)
1 (True)
1 (True)
0xFF (default)
SNVT type
SNVT_lev_percent
SNVT_lev_percent
SNVT_rpm
SNVT_freq_hz
SNVT_time_sec
SNVT_time_sec
SNVT_time_sec
Value:
Any
0
1-200
201-255
Any
Value:
Min:
Max:
-163.840%
+163.830%
TR200
Profile
parame-
ter
VSD 6010
4-13
VSD 6010
4-11
VSD 6010
1-25
VSD 6010
1-23
VSD 6010
3-41
VSD 6010
3-42
VSD 6010
-
Command:
Stop
Running 0%
Running 0.5% to 100%
Running 100%
AUTO (invalid, no action)
Resolution:
0.005%
TR200 LonWorks