Trane LonWorks TR200 Instruction Manual page 40

Option module
Table of Contents

Advertisement

Output Current
Variable
SNVT
name:
type:
nvoDrvCurnt
SNVT_amp
This variable contains the adjustable frequency drive output current in ampere measured as a mean value, IRMS.
The value is filtered and therefore approximately 1.3 seconds delayed before a current change is reflected in the
output variable.
Output Voltage
Variable
SNVT
name:
type:
nvoDrvVolt
SNVT_volt
This variable contains the adjustable frequency drive output voltage.
Output Power
Variable
SNVT
name:
type:
nvoDrvPwr
SNVT_power_kilo
This variable contains the adjustable frequency drive output power in kW, calculated on the basis of the actual
motor voltage and current.
The value is filtered and therefore approximately 1.3 seconds delayed before a power change is reflected in the
output variable.
Running Hours
Variable
SNVT
name:
type:
nvoDrvRunHours
SNVT_time_hour
This variable contains the total running hours of the motor.
TR200 LonWorks
Configuration of the system
Value:
Min:
Max:
0 A
3,276.6 A
Value:
Min:
Max:
0 V
3,276.6 V
Value:
Min:
Max:
0 kW
6,554.4 kW
Min:
0 hr
65,534 hr
Resolution:
0.1 A
Resolution:
0.1 V
Resolution:
0.1 kW
Value:
Max:
Resolution:
1 hr
5-19