Configuration of the system
kWh Counter [kWh]
Variable
SNVT
name:
type:
nvoDrvEnrg
SNVT_elec_kwh_l
This variable contains the power consumption of the motor in kWh measured as a mean value over a one hour
period.
DC Link Voltage [V]
Variable
SNVT
name:
type:
nvoDCVoltage
SNVT_volt
This variable contains the measured DC link voltage. The value is filtered and therefore may be delayed with up
to 1.3 seconds before a voltage change is reflected in the output variable.
Motor Thermal [%]
Variable
SNVT
name:
type:
nvoTempMrt
SNVT_lev_cont
This variable contains the calculated / estimated thermal load on the motor.
The cut-out limit is at 100%.
Inverter Thermal [%]
Variable
SNVT
name:
type:
nvoTempInvrtr
SNVT_lev_cont
This variable contains the percentage thermal load of the inverters.
The cut-out limit is at 100%.
Closed-loop Feedback
Variable
SNVT
name:
type:
nvoFeedback
SNVT_count_inc_f
This variable contains the summarized amount of network feedback in closed-loop mode.
5-10
Value:
Min.
Max.
0 kWh
219,748,364.8 kWh
Value:
Min.
Max.
0 V
10,000 V
Value:
Min.
Max.
0 %
100 %
Value:
Min.
Max.
0 %
100 %
Value:
Min.
Max.
0 %
100 %
Resolution:
1 kWh
Resolution:
0.1 V
Resolution:
0.5%
Resolution:
0.5%
Resolution:
0.5%