Trane LonWorks TR200 Instruction Manual page 35

Option module
Table of Contents

Advertisement

Configuration of the system
Analog Input (54)
Variable
SNVT
name:
type:
nvoAnIn1
Changeable
SNVT_volt
SNVT_amp_mil
SNVT_lev_percent
This variable contains the value allocated to the analog input terminal 54.
This terminal can either be configured as a voltage input (0–10 V) or as a current input (0–20 mA), depending
on the setting of switch S 202. The variable type is changeable with the commissioning tool in order to match
the appropriate unit.
If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V/mA to par.6-21
High Voltage
or par.6-23
Analog Input (X30/11)
Variable
SNVT
name:
type:
nvo101AnIn1
Changeable
SNVT_volt
SNVT_lev_percent
This variable contains the value allocated to the analog input terminal X30/11 of the
MCB101
.
If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V to par.6-31
High
Voltage.
This variable is available only if the General Purpose I/O option (MCB101) has been installed.
5-14
Terminal 54 High Current
Value:
Min.
Max.
0 V
10 V
0 mA
20 mA
0 %
100 %
Value:
Min.
Max.
0 V
10 V
0 %
100 %
Resolution:
0.1 V
0.1 mA
0.1%
Terminal 54
Resolution:
0.1 V
0.1%
General Purpose I/O option,
Terminal X30/11
TR200 LonWorks