Trane LonWorks TR200 Instruction Manual page 48

Option module
Table of Contents

Advertisement

Bit 05, Hold output frequency:
Bit 05 set to [0] causes the present output frequency
(Hz) to freeze. The frozen output frequency can then
be changed only by means of the digital inputs set by
par. 5-10 to 5-15, programmed to [Speed up] or
[Slow].
If [Freeze output] is active, the adjustable frequency
drive can only be stopped by the following:
Bit 03 Coasting stop
Bit 02 DC braking
Digital input (par. 5-10 to 5-15) programmed
to DC braking, Coasting stop or Reset and
coasting stop.
Bit 06, Ramp stop/start:
Bit 06 set to [0] causes a stop, in which the motor
speed is ramped down to stop via the selected ramp-
down parameter.
Bit 06 set to [1] permits the adjustable frequency drive
to start the motor if other starting conditions have
been fulfilled.
NOTE
In par.8-53
Start
Select, a selection is made to define
how Bit 06 Ramp stop/start gates with the corresponding
function on a digital input.
Bit 07, Reset:
Bit 07 set to [0] means no reset.
Bit 07 set to [1] resets a trip. Reset is activated on the
leading edge of the signal, i.e., when changing from
logic '0' to logic '1'.
Bit 08, Jog:
Bit 08 set to [1] causes the output frequency to be de-
termined by par.3-19
Jog Speed
Bit 09, Selection of ramp:
Bit 09 set to [0] means that ramp 1 is active (par. 3-40
to 3-47).
Bit 09 set to [1] means that ramp 2 (par. 3-50 to 3-57)
is active.
Bit 10, Data not valid / Data valid:
This bit tells the adjustable frequency drive whether
the control word is to be used or ignored. Bit 10 set
to [0] causes the control word to be ignored.
TR200 LonWorks
[RPM].
How to Control the Adjustable Frequency
Bit 10 set to [1] causes the control word to be used.
The control word is always contained in the telegram,
regardless of which type of message is used, so this
function is useful for 'turning off' the control word
when not required for updating or for reading pa-
rameters.
Bit 11, Relay 01:
Bit 11 set to [0] means that Relay is not activated.
Bit 11 set to [1] activates Relay 01, provided
word bit 11
[36] has been chosen in par.5-40
Relay.
Bit 12, Relay 04:
Bit 12 set to [0] means that Relay 04 has not been ac-
tivated.
Bit 12 set to [1] activates Relay 04, provided
word bit 12
[37] has been chosen in par.5-40
Relay.
Bit 13 and 14, Selection of set-up:
Bits 13 and 14 are used to select one of four menu set-
ups according to the following table:
Set-up
Bit 14
1
2
3
4
The function is only possible when Multi-Set-up [9] is
selected in par.0-10
Active
In par.8-55
Set-up
Select, a selection is made to define
how Bit 13/14 gates with the corresponding function
on the digital inputs.
Bit 15, Reverse:
Bit 15 set to [0] causes no reversing.
Bit 15 set to [1] causes reversing.
Note: par.4-10
Motor Speed Direction
reversing is possible.
Drive
Control
Function
Control
Function
Bit 13
0
0
0
1
1
0
1
1
Set-up.
determines if
6-3

Advertisement

Table of Contents
loading

Table of Contents