Parameters; Parameter List; Parameter Group 8 - Trane LonWorks TR200 Instruction Manual

Option module
Table of Contents

Advertisement

Parameters

Parameter List

Parameter List
Par.
Parameter name:
No.
8-01
Control Site
8-02
Control Word Source
8-03
Control Word Timeout Time
8-04
Control Word Timeout Function
8-05
End-of-timeout Function
8-06
Reset Control Word Timeout
8-07
Diagnosis Trigger
8-10
Control Word Profile
8-50
Coasting Select
8-52
DC Brake Select
8-53
Start Select
8-54
Reversing Select
8-55
Set-up Select
8-56
Preset Reference Select
11-00
Neuron ID
11-10
Drive Profile
11-15
Lon Warning Word
11-18
LonWorks Revision
11-21
Store Data Values

Parameter Group 8-**

8-01 Control Site
Option:
[0] *
Digital and ctrl. word
[1]
Digital only
[2]
Control word only
8-02 Control Source
Option:
TR200 LonWorks
Default value:
Dig. and control word [0]
FC Port [1]
600 s
Off [0]
Hold set-up [0]
Do not reset [0]
Disable [0]
FC profile [0]
Logic OR [3]
Logic OR [3]
Logic OR [3]
Logic OR [3]
Logic OR [3]
Logic OR [3]
00 00 00 00 00 00
VSD 6010 [0]
0
[0, 10]
Off [0]
Function:
The setting in this parameter overrides the settings in par.8-50
Select
to par.8-56
Preset Reference
Control by using both digital input and control word.
Control by using digital inputs only.
Control by using control word only.
Function:
Select the source of the control word: one of two serial interfaces or four
installed options. During initial power-up, the adjustable frequency drive
automatically sets this parameter to
communication bus option installed in slot A. If the option is removed,
the adjustable frequency drive detects a change in the configuration, sets
par.8-02
Control Source
back to default setting
Drive Port
, and the adjustable frequency drive then trips. If an option is
installed after initial power-up, the setting of par.8-02
Conver-
Range:
sion type:
[0 - 2]
-
[0 - 4]
-
0.1–18000
1
[0 - 10]
-
[0 - 1]
-
[0 - 1]
-
[0 - 3]
-
[0 - x]
-
[0 - 3]
-
[0 - 3]
-
[0 - 3]
-
[0 - 3]
-
[0 - 3]
-
[0 - 3]
-
-
-
-
-
-
-
-
-
[0 - 1]
-
Select.
Option A
[3] if it detects a valid serial
Adjustable Frequency
Control Source
Data
type:
5
5
7
5
5
5
5
5
5
5
5
5
5
5
10
5
6
9
5
Coasting
will
8-1