Temperature Display At Keypad - NAPCO GEMINI GEM-P1664 Programming Instructions Manual

Control panel/communicator
Hide thumbs Also See for GEMINI GEM-P1664:
Table of Contents

Advertisement

Page 42
TEMP ERATURE DISPLAY A T KE YPAD (A DDRES S 1666-1668)
LEFT DATA
Temperature Lower Limit*
VALUES
Binary Temperature Value 16°
Binary Temperature Value 32°
Binary Temperature Value 64°
Enable for Negative
Temperature Value
LEFT DATA
Temperature Upper Limit*
VALUES
Binary Temperature Value 16°
Binary Temperature Value 32°
Binary Temperature Value 64°
Enable for Negative Tempera-
ture Value
LEFT DATA
Enable Temperature Options*
VALUES
Reserved
Reserved
Reserved
Reserved
Temperature Display at the Keypad
The temperature is displayed instead of the date on line 2 of the GEM-RP1CAe2 and GEM-K1CA keypads only. The keypads listed
on the cover of this manual are able to program, but not display, this Temperature Display feature.
The GEM-RP1CAe2 / GEM-K1CA keypad will display from –22F to 140F (or -30C to 60C). Fahrenheit is the default setting, select
Celsius by enabling address 1668 option 2 (right nibble). When this Temperature Display Option is enabled, Zone 6 becomes the
input for the GEM-TEMP64 Temperature Sensor module and Zone 6 of the panel becomes inoperative; if Zone Doubling is se-
lected, zones 6, 14 will be inoperative.
Address 1668 option 3 (right nibble) enables Zone 6 to report a temperature problem. Address 1666 (options 1-7) set the lower limit
temperature value and address 1667 (options 1-7) sets the upper limit temperature value (both values are set in binary). If the tem-
perature detected by the panel is above or below these set limits, the panel will report an alarm on Zone 6. To function and report
properly, Zone 6 must be selected as a reporting zone, 24hr zone in area 1 and auto-resetable. At both 1666 and 1667 addresses,
option 8 sets positive or negative temperature. If the temperature of 0 degrees is required, "negative zero" (-0) degrees must be
used (+0 or an empty location is not a valid temperature). To simulate the sensor module, a power supply can be connected to
Zone 6 and set from .55v to 3.05v to display the whole temperature range. Temperature values are read and updated every 5 sec-
onds. To report an outer limit temperature, the temperature must be out of limits for 2 seconds. To avoid false alarm reports, the
limits have a threshold of 5 degrees in the software. Two new logs have been created for temperature out of limits and restore. If
the
key is depressed and held down for 2 seconds, the date will display for 5 seconds.
G
In addition, three addresses must be enabled (either via Quickloader or via direct address programming) in order for the Tempera-
ture Display at Keypad feature to operate.
The following features must be enabled In Quickloader (or in direct address programming):
1. Keypad Assignment, Temperature Settings tab, Enable Temperature Display (Address 1668, option 1)
2. Keypad Assignment, Keypad Features tab, Enable Keypad Time/Date Display (Address 1420, option 7)
3. Keypad Assignment, Keypad Features tab, Enable Set Time/Date Message (Address 2051, option 1)
Note: If these three addresses are set and power (AC and battery) are subsequently removed, they keypad will indicate that the
time and date are lost and will need to be reset. See WI1425 for more information.
*This feature not evaluated by UL.
X
GEM-P1664 Programming Instructions
- - Z O N E 6 T E M P E R AT U R E S E N S O R - -
ADDRESS 1666
LEFT DIGIT (SUM
1
OF DATA VALUES)
2
4
[Default = blank (•) blank (•)]
8
*This feature not evaluated by UL.
ADDRESS 1667
LEFT DIGIT (SUM
1
OF DATA VALUES)
2
4
[Default = blank (•) blank (•)]
8
*This feature not evaluated by UL.
ADDRESS 1668
LEFT DIGIT (SUM
1
OF DATA VALUES)
2
4
[Default = blank (•) blank (•)]
8
*This feature not evaluated by UL.
RIGHT DATA
RIGHT DIGIT (SUM
OF DATA VALUES)
RIGHT DATA
RIGHT DIGIT (SUM
OF DATA VALUES)
RIGHT DATA
RIGHT DIGIT (SUM
OF DATA VALUES)
L
WI1423A 1/06
VALUES
Temperature Lower Limit*
1
Binary Temperature Value 1°
2
Binary Temperature Value 2°
4
Binary Temperature Value 4°
8
Binary Temperature Value 8°
VALUES
Temperature Upper Limit*
1
Binary Temperature Value 1°
2
Binary Temperature Value 2°
4
Binary Temperature Value 4°
8
Binary Temperature Value 8°
VALUES
Enable Temperature Options*
1
Enable Temperature
Display Option
2
Select Degrees Celsius
4
Report Temperature Alarm
(Zone 6)
8
Reserved
NAPCO Security Systems