NAPCO GEMINI GEM-P1664 Programming Instructions Manual page 28

Control panel/communicator
Hide thumbs Also See for GEMINI GEM-P1664:
Table of Contents

Advertisement

Page 28
LEFT DATA
SYSTEM OPTIONS
VALUES
(CIRCLE
RESERVED
1
Enable AutoArm if not
2
closed at end of Window
Enable Keypad Time/
4
Date Display
Disable Zone Fault
8
Scrolling
LEFT DATA
SYSTEM OPTIONS
VALUES
(CIRCLE
Access Control on
1
PGM2 Output
Maintained Keyswitch
2
Arming
Enable Manager's Mode
4
Disable Keypad Instant
8
Mode
LEFT DATA
SYSTEM OPTIONS
VALUES
(CIRCLE
Disable Keypad Function
1
Mode Download
Disable Callback
2
Download
Chirp Output on Keyfob
4
Arm/Disarm
Change Pulse Output to
8
§
Temporal Output
LEFT DATA
SYSTEM OPTIONS
VALUES
(CIRCLE
Line-Fault Test only
1
when Armed**
Enable Line-Fault Test**
2
Inhibit System Trouble
UL
4
Audible at Keypad
Select Alarm Output for
8
Keyfob Chirp
NOTE: Not for UL Installations.
LEFT DATA
SYSTEM OPTIONS
VALUES
(CIRCLE
Don't Clear PGM2 Output
1
with Disarm
Disable 2nd Call Ans.
2
Machine Override
RESERVED
4
Disable Code Required
8
for EZ Bypass
1. Select the desired option by circling
each digit (left and right).
2. Add the data values (ex: F=15=(1+2+4+8) from the selected
options. See page 23).
3. Enter in address location (left and right digits). NOTE: Dark
shaded data value box shows option not available.
U
D
4. Press
or
to save.
X
GEM-P1664 Programming Instructions
SYSTEM OPT ION S (ADDRES S 1420-1424)
ADDRESS 1420
)
LEFT DIGIT (SUM
OF DATA VALUES)
[Default = blank (•) blank (•)]
ADDRESS 1421
)
LEFT DIGIT (SUM
OF DATA VALUES)
[Default = blank (•) blank (•)]
)
ADDRESS 1422
LEFT DIGIT (SUM
OF DATA VALUES)
[Default = blank (•) blank (•)]
§
This feature must be programmed in Fire
Alarm applications.
)
ADDRESS 1423
LEFT DIGIT (SUM
OF DATA VALUES)
[Default = blank (•) blank (•)]
For Address 1423: Default depends on Easy
EZ ZONE DOUBLING? Y/N
Menu Question "
If yes, then [Default = •(blank) 1].
If no, then [Default = •(blank) •(blank)].
)
ADDRESS 1424
LEFT DIGIT (SUM
OF DATA VALUES)
[Default = blank (•) blank (•)]
the data values for
RIGHT DIGIT (SUM
OF DATA VALUES)
RIGHT DIGIT (SUM
OF DATA VALUES)
RIGHT DIGIT (SUM
OF DATA VALUES)
RIGHT DIGIT (SUM
OF DATA VALUES)
".
RIGHT DIGIT (SUM
OF DATA VALUES)
*NOTE: Address 1423: Default depends on Easy Menu Question :"EZ
ZONE DOUBLING? Y/N". If yes, then [Default = 1]. If no, then [Default =
blank (•)].
**NOTE: To select "Line-Fault Test only when Armed", you must also
select "Enable Line-Fault Test" at address 1423.
***NOTE: If "Enable Global Ambush Code" in Address 1422 is selected,
then program the 2-digit "Global Ambush Code" in Address 2045. If
Address 2045 is left blank (•), then, the 2-digit "Global Ambush Code"
will be "99".
L
WI1423A 1/06
RIGHT DATA
VALUES
SYSTEM OPTIONS
)
(CIRCLE
Opening Report Only after
1
Alarm Report
Closing Report Only on
2
Conditional Close
Incl. Sel./Grp. Bypass in
4
Cond. Close /Status
Status Report
8
RIGHT DATA
VALUES
SYSTEM OPTIONS
)
(CIRCLE
Auto Bell Test
1
on Arming
Auto Reset after Burglary
2
Output Timeout
Suppress Bypass
4
Reminder when Armed
Enable Local Alarm on
8
First Zone AND Trip
RIGHT DATA
VALUES
SYSTEM OPTIONS
)
(CIRCLE
Interior Normally By-
1
passed
Enable Global Ambush
2
Code ***
Reset Day Zone with Arm/
4
Disarm Only
Enable Residential Fire
8
RIGHT DATA
VALUES
SYSTEM OPTIONS
)
(CIRCLE
Enable Zone Doubling
1
(Zones 9-16)
Wireless Trouble
2
Activates Telco 1
Wireless Trouble
4
Activates Telco 3
Enable Alarm Output on Telco
8
Fail only when Armed
RIGHT DATA
VALUES
SYSTEM OPTIONS
)
(CIRCLE
Automatic Interior Bypass/
1
Easy Exit
Veri-phone Zones Trip
2
PGM2 Output
Veri-phone Audio Priority
4
Over Alarms
Resound on Wireless
8
Smoke Low Battery
NAPCO Security Systems