16.3.6 To provide drainage
General guidelines
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
4 Pass the drain hose and refrigerant pipes through the wall hole.
5 When the complete installation is finished (drain piping
4
drainage" [
59], the refrigerant piping
the electrical wiring
the mounting plate
Make sure condensation water can be evacuated properly. This involves:
▪
General guidelines
▪
Connecting the drain piping to the indoor unit
▪
Checking for water leaks
▪
Pipe length. Keep drain piping as short as possible.
▪
Pipe size. Keep the pipe size equal to or greater than that of the connecting pipe
(vinyl pipe with nominal Ø13 mm).
(mm)
NOTICE
▪
Install the drain hose with a downward slope.
▪
Traps are NOT permitted.
▪
Do NOT put the end of the hose in water.
▪
Drain hose extension. When extending the drain hose, use a field supplied
extension hose with nominal Ø13 mm. Do NOT forget to use a heat insulation
tube on the indoor section of the extension hose.