To Connect The Refrigerant Piping To The Indoor Unit - Daikin FAA71BUV1B Installer And User Reference Manual

Split system air conditioner
Hide thumbs Also See for FAA71BUV1B:
Table of Contents

Advertisement

17
|
Piping installation

17.2.6 To connect the refrigerant piping to the indoor unit

Installer and user reference guide
66
a
a Flare's inner surface MUST be flawless.
b The pipe end MUST be evenly flared in a perfect circle.
c Make sure the flare nut is fitted.
CAUTION
Install the refrigerant piping or components in a position where they are unlikely to
be exposed to any substance which may corrode components containing refrigerant,
unless the components are constructed of materials that are inherently resistant to
corrosion or are suitably protected against corrosion.
WARNING: MILDLY FLAMMABLE MATERIAL
The R32 refrigerant (if applicable) in this unit is mildly flammable. Refer to the
outdoor unit specifications for the type of refrigerant to be used.
Pipe length. Keep refrigerant piping as short as possible.
1 Flare connections. Connect refrigerant piping to the unit using flare
connections.
2 Insulation. Insulate the refrigerant piping, the insulating tape should be
wrapped from the L-shaped bend all the way to the end inside the unit as
follows:
a
b
c
d
a Field piping
b Indoor unit piping insulation tubing
c Indoor unit piping
d Insulating tubing tape
e Insulating tape (accessory)
f Large tie wrap (accessory)
g Beginning of wrapping
h L-shaped bend
i Insulation tubing seam (make sure there are no gaps in the insulation tubing seam)
NOTICE
Make sure to insulate all refrigerant piping. Any exposed piping might cause
condensation.
b
c
b
d
e
f
i
g
h
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Faa100buv1b

Table of Contents