18.1.3 Specifications of standard wiring components

18.2 To connect the electrical wiring to the indoor unit

FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
Wire type
Stranded conductor wire
with round crimp-style
terminal
Tightening torques
Wiring
Interconnection cable
(indoor↔outdoor)
User interface cable
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
Component
Interconnection cable (indoor↔outdoor)
User interface cable
(a)
In case the conduit pipes are not used, use H07RN-F (60245 IEC 66).
NOTICE
Follow the wiring diagram (delivered with the unit, located at the inside of the
service cover).
For instructions on how to connect the optional equipment, see the installation
manual delivered with the optional equipment.
Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
c b
B
a
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
Screw size
M4
M3.5
1-3
18
Electrical installation
|
Installation method
a
b
c
B
Tightening torque
(N•m)
1.18~1.44
0.79~0.97
Specification
2
4-core cable 1.5 mm
~2.5 mm
applicable for 220~240 V
H05RN-F (60245 IEC 57)
Vinyl cords with 0.75 to 1.25 mm²
sheath or cables (2‑core wires)
H03VV-F (60227 IEC 52)
Maximum 500 m
Installer and user reference guide
2
and
(a)
69