11. Long-Term Storage

WARNING : INJURY
Always turn the starter switch to the STOP position and stop the engine, then
close and lock OPERATION PANEL DOOR before checking or maintaining
the engine or any equipment.
CAUTION : FIRE
Always be sure to wipe up any spilled fuel or oil.
Allow the generator to cool before covering with the protective cover.
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after
stopping the engine as they are still extremely hot.
(1) Storage Procedures
Perform the following maintenance procedures before storing this generator if it is not going
to be used for two months or more.
1
Remove the battery. (Refer to section "8-6. Checking the Battery".)
Replace the engine oil.
2
(Refer to section "10. Inspection/Maintenance (1) Engine Oil Replacement".)
Drain the fuel from the fuel tank and filter.
3
(Refer to section "10. Inspection/Maintenance (5) Draining Water from the Fuel
Tank".)
4
Clean up and inspect inside of the spill containment.
(Refer to section "10. Inspection/Maintenance (10) Spill Containment
Cleaning/Inspection".)
5
Remove the starter key and store in a secure location.
Clean up all generator components, and store in a dry and dust-free location. Also cover
6
when storing so that rain cannot enter through the suction or exhaust ports.
< Note >
Maintain proper fluid level of the removed battery and recharge approximately every month.