Grid Settings; 圖5-13 : Grid Settings 頁面 - Delta RPI Series Operation And Installation Manual

Grid-tie transformerless solar inverter
Hide thumbs Also See for RPI Series:
Table of Contents

Advertisement

5.2.7.4 Grid Settings

Grid Settings頁面包含各種電壓與頻率保護值,這些保護值乃依據各電力法規所
建立,若無特殊需求請勿修改任何保護值。
Inverter ID: 002
Insulation
Country
Grid Settings
ENT
Voltage Protection
Freq. Protection
Reconnect T
P Ramp Up
6000%/m
EXIT
Voltage Protection
Freq. Protection
EXIT
Reconnect T
P Ramp Up
6000%/m
圖5-13 : Grid Settings 頁面
ENT
High Off
High On
600s
High Off T
Low Off
EXIT
Low On
Low Off T
EXIT
Hi Off Slow
Hi On Slow
Hi Off Sl T
Lo Off Slow
EXIT
Lo On Slow
Lo Off Sl T
ENT
High Off
High On
600s
High Off T
Low Off
EXIT
Low On
Low Off T
EXIT
Hi Off Slow
Hi On Slow
Hi Off Slow T
Lo Off Slow
EXIT
Lo On Slow
Lo Off Slow T
189
變流器開機
276.0V
259.0V
0.3s
If user enters wrong settings
184.0V
Wrong Settings
219.0V
0.3s
Press ▲&▼ 5s
276.0V
259.0V
Do you want to set
U to the max range?
Yes / ►No
600.0s
184.0V
219.0V
1.0s
51.50Hz
50.05Hz
0.1s
If user enters wrong settings
47.50Hz
Wrong Settings
47.55Hz
0.1s
65.00Hz
Press ▲&▼ 5s
64.95Hz
Do you want to set
F to the max range?
Yes / ►No
5.0s
45.00Hz
45.55Hz
5.0s