7 Error message and Trouble Shooting
Message
1. Actual utility frequency is over
AC Freq
the OFR setting
High
2. Incorrect country setting
(E01)
3. Detection circuit malfunction
1. Actual utility frequency is under
AC Freq
the UFR setting
Low
2. Incorrect country or Grid setting
(E02)
3. Detection circuit malfunction
Grid Quality
Non-linear load in Grid and near
(E07)
to inverter
HW Con.
1. Wrong connection in AC plug
Fail
2. Detection circuit malfunction
(E08)
No Grid
1. AC breaker is OFF
(E09)
2. Disconnect in AC plug
1. Actual utility voltage is under
AC Volt
the UVR setting
Low
2. Incorrect country or Grid setting
(E10, E15,
3. Wrong connections in AC plug
E20)
4. Detection circuit malfunction
1. Actual utility voltage is over the
AC Volt
OVR setting
High
2. Utility voltage is over the Slow
(E11, E13,
OVR setting during operation
E16, E18,
3. Incorrect country or Grid setting
E21, E23)
4. Detection circuit malfunction
EPO
1. EPO is activated by user
2. Detection circuit malfunction
(E25)
Solar1
1. Actual Solar1 voltage is over
High
1000Vdc
2. Detection circuit malfunction
(E30)
Solar2
1. Actual Solar2 voltage is over
High
1000Vdc
2. Detection circuit malfunction
(E31)
ERROR
Possible cause
Error message and Trouble Shooting
1. Check the utility frequency on the
inverter terminal
2. Check country setting
3. Check the detection circuit inside the
inverter
1. Check the utility frequency on the
inverter terminal
2. Check country & Grid setting
3. Check the detection circuit inside the
inverter
Grid connection of inverter need to be
far away from non-linear load if necessary
1. Check the AC connection, must accords
to manual
2. Check the detection circuit inside the
inverter
1. Switch on AC breaker
2. Check the connection in AC plug and
make sure it connects to inverter
1. Check the utility voltage connection
to the inverter terminal
2. Check country & Grid setting
3. Check the connection in AC plug
4. Check the detection circuit inside the
inverter
1. Check the utility voltage on the inverter
terminal
2. Check the utility voltage on the inverter
terminal
3. Check country & Grid setting
4. Check the detection circuit inside the
inverter
1. Release the EPO button
2. Check the detection circuit inside the
inverter
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2. Check the detection circuit inside the
inverter
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2. Check the detection circuit inside the
inverter
57