After wiring, installer should choose the AC connection type on the control
panel. About setting, please refer to 5.2.7 Install Settings.
The AC voltage should be as followings:
3P3W
L1-L2: 400 Vac ± 20%
L1-L3: 400 Vac ± 20%
L2-L3: 400 Vac ± 20%
4.2.2 Permitted earthing systems
Earthing system
Permitted
TT is not recommended. The voltage of N has to be very close to PE.
(difference <20 V
3P4W
L1-N: 230 Vac ± 20%
L2-N: 230 Vac ± 20%
L3-N: 230 Vac ± 20%
TN-S
TN-C
Yes
Yes
)
rms
27
TN-C-S
TT
Yes
Yes
Wiring
IT
No