5.2.7.4 Grid Settings
Grid Settings页面包含各种电压与频率保护值,这些保护值乃依据各电力法规所
建立,若无特殊需求请勿修改任何保护值。
Inverter ID: 002
Insulation
Country
►
Grid Settings
ENT
►
Voltage Protection
Freq. Protection
Reconnect T
P Ramp Up
6000%/m
EXIT
Voltage Protection
►
Freq. Protection
EXIT
Reconnect T
P Ramp Up
6000%/m
图5-13 : Grid Settings 页面
ENT
High Off
►
High On
600s
High Off T
Low Off
EXIT
►
Low On
Low Off T
EXIT
Hi Off Slow
Hi On Slow
►
Hi Off Sl T
Lo Off Slow
EXIT
Lo On Slow
Lo Off Sl T
ENT
High Off
►
High On
600s
High Off T
Low Off
EXIT
►
Low On
Low Off T
EXIT
Hi Off Slow
Hi On Slow
Hi Off Slow T
►
Lo Off Slow
EXIT
Lo On Slow
Lo Off Slow T
115
逆变器开机
276.0V
259.0V
0.3s
If user enters wrong settings
184.0V
Wrong Settings
219.0V
0.3s
Press ▲&▼ 5s
276.0V
259.0V
Do you want to set
U to the max range?
Yes / ►No
600.0s
184.0V
219.0V
1.0s
51.50Hz
50.05Hz
0.1s
If user enters wrong settings
47.50Hz
Wrong Settings
47.55Hz
0.1s
65.00Hz
Press ▲&▼ 5s
64.95Hz
Do you want to set
F to the max range?
Yes / ►No
5.0s
45.00Hz
45.55Hz
5.0s