6.4 Active Power Control

6.4.1 Grid protection settings

The setting of this function can be found
in the "Grid Setting" page, please refer to
previous sub-chapter for the instruction to
access to this page.
Installers can adjust settings to meet the
requirements from the grid operator.
Passive anti-islanding voltage limit values.
Protective function
Undervoltage 2
(Vac Low Off)
Undervoltage 1
(Vac Low Off Slow)
Overvoltage 1
(Vac High Off Slow2)
Overvoltage 2
(Vac High Off)
Passive anti-islanding grequency limit values
Region
Protective function
limit value
Under
Trip delay time
frequency 1
Maximum
disconnection time
Protective function
limit value
Over
Trip delay time
frequency 1
Maximum
disconnection time
Active/Reactive Power Control and LVRT (Optional)
Protective
Trip delay time
function limit
70 V
180 V
265 V
275 V
Australia
A
47Hz
1s
2s
52Hz
-
0.2s
27
Maximum
disconnection time
1s
10s
1s
-
Australia
Australia
B
C
47Hz
45Hz
1s
5s
2s
6s
55Hz
52Hz
-
-
0.2s
0.2s
2s
11s
2s
0.2s
New
Zealand
45Hz
1s
2s
55Hz
-
0.2s